Overview
The ADF400L series multi-user electric energy meter can achieve up to 12 three-phase or 36 single-phase direct
access measurement or 12 three-phase mutual inductor access measurement, a hybrid of direct access and mutual
inductor access through module combination measurement method. This series of electric energy meters are popular among communities, schools, enterprises, etc. due to their high accuracy, centralized installation, centralized management, high installation flexibility, and non-interference.
Function&Parameter
Features | Function Description |
Energy metering | Total active energy, forward and reverse active energy, multi-rate active energy measurement |
Electricity measurement | U,I |
P,Q,S,PF,F | |
LCD display | 8-digit segment LCD display, backlight display |
Button programming | Key programmable communication, number of loops, single three-phase mode, external control mode and other parameters |
Pulse output | Active pulse output |
Multiple rate | Support 4 time zones, 2 time slots, 14 daily time slots, 4 rates |
Date, time, day of the week | |
Main module communication | Infrared communication |
Up to 3 channels of communication: RS485 interface, Also support Modbus |
|
Prepaid agreement (remote, radio frequency card) | Cost control (including forward active power and reverse active power) |
Time control | |
Negative control (malignant load identification) | |
Strong control | |
Recharge record | 20 Article |
technical parameter model | ADF400L | |
Auxiliary power | Voltage | Three-phase 3*220V/380V power supply (for single-phase power supply, short-circuit terminals 1, 2, and 3 on the instrument) |
Power consumption | ≤10W | |
Voltage input | Rated voltage | 3×220/380V,3×57.7/100V, |
Reference frequency | 50Hz | |
Current input | Input Current | 3×1(6)A(Instrument transformer access), 3*10 (80) (direct access) |
Starting current | 1‰Ib | |
Measuring performance | measurement accuracy | 0.5s level |
Clock accuracy | ≤0.5s/d | |
Pulse | Pulse output | Each three-phase metering module has 1 active energy pulse |
Pulse Width | 80ms±20ms | |
Pulse constant | 3×1(6)A specification 6400 imp/kWh | |
3×10(80)A specification 400 imp/kWh | ||
Switch | Main module | Main module 2DI+2DO,Among them, DI is dry contact input |
Slave module | Transformer access slave module 4DI+4DO,Among them, DI is 220V wet contact input | |
Communication | Infrared interface | Infrared communication |
RS485 interface | MODBUS-RTU | |
Ethernet interface | Modbus-TCP,TCP/IP | |
Surroundings | temperature | Operating temperature:-20ºC~+60ºC, storage temperature:-30ºC~+70ºC |
humidity | ≤95%RH,No condensation, no corrosive gas place | |
altitude | ≤2000m |
Dimension
Wiring