Product Description
AMC16Z-ZA main circuit 2 channel 3 phase dual source energy meter ac power meter with switch output is a measuring device designed specifically
for the power supply management of server in the data center.
Such device is small and exquisite in design, capable of centralized monitoring on various electric parameters and on-off states of dozens of
circuits,including incoming line circuit and outgoing line circuit, and it achieves the highly integration of monitoring circuits in volume.
AMC16Z-ZA main circuit incoming line measuring meter is usually used together with our outgoing line multi channel energy meter AMC16Z-FAK24
or FAK48 in data center or POC project.
Functions and Parameters
Functions of AMC16Z-ZA dual source energy meter main
circuit incoming line measuring meter
Measure A+B main circuits dual source 2 channel 3 phase ac bus voltage,current,active power,reactive power,apparent power,power factor,active energy,reactive energy,zero to earth voltage,neutral current
Measuring A+B dual source main circuit incoming line
6 channel passive switching value input
2 channel switching value output
1 channel RS485
2-31th harmonics
Optional functions:
temperature and humidity sensor
Leakage current sensor
Datasheet
Data of main circuit 2 channel 3 phase energy meter AMC16Z-ZA |
Measured parameters |
Voltage, current, frequency, active power, reactive power, power factor, active power, reactive power
|
Zero ground voltage, neutral line current, total harmonic content (THD), 2-63st harmonics, current and voltage unbalance degree, current K coefficient (KF), voltage crest coefficient (CF), telephone waveform factor (THFF), peak voltage, voltage and current sequence quantity, environmental temperature and humidity. |
Bus voltage |
Rated |
220VAC |
Measurement range |
±20% |
Overload |
Instant voltage 2times/second |
incoming line current |
Rated |
Secondary current 5A by CTs |
Range |
0~6A |
Overload |
Duration 1.2 times, instantaneous 10 times/second |
Input frequency |
45~60Hz |
Accuracy |
Inlet wire |
Voltage/current level 0.2, active power/electric energy level 0.5, reactive power/electric energy level 1 |
Temp |
±1ºC |
Humidity |
±5% |
Switching value output |
2-way 3A 250VAC/3A 30VDC |
Switch input |
6-way dry contact |
Communication |
RS485 Modbus-RTU |
Installation |
Din rail 35mm or bottom panel mounted |
Remark:AMC16Z-ZA is for 2 main circuits incoming line measurement,it is usually used together with outgoing line multi channel meter AMC16Z-FAK24 or AMC16Z-FAK48 in the data center.