Type
|
Function
|
AMC16MA
|
Three Phase: 2 Channels Inlet I, U, P, Q, EP, EQ, S
Single Phase: 36 Channels Outlet (Three Phase 12 Channels Outlet) I, U, P, Q, EP, EQ
1DO, RS485 (Modbus-RTU)
|
AMC16MAH
|
Measure the Total Three Phase Incoming Line Voltage, Two Three-phase Incoming Lines I, kW, kvar, cosΦ, kWh, kvarh (Required Configure AKH-0.66W 100A/20mA Current Transformer); Measure Incoming Line Voltage, Incoming Line Current, Outgoing Line Current 2-15 Sub-Harmonics and Total Harmonics; 1 RS485 Communication; 1DO, AC220V Power Supply
|
AMC16Z-ZA
|
A+B Independent 2 Channels Three-phase Inlet U, I, P, Q, S, PF, EP, EQ, UN to PG, Neutral Current 2-63rd Harmonic of Voltage and Current 6 Channels Passive Switching Input 2 Channels Switching Output RS485 (Modbus-RTU) Communication
|
AMC16Z-ZD
|
Measurement of A+B Independent 2-way DC Bus Voltage, Current, kW, kWh, 6DI+2DO+1RS485 (Modbus-RTU)
|
AMC16Z-KA
|
A+B Independent 2 Way Unilateral 24 Active Switch States
|
AMC16Z-KD
|
A+B Independent 2 Way Unilateral 24 Passive Switch States
|
AMC16Z-FAK24
|
Measure A+B Two-way AC Outlet, Total 24 Branch Full Electric Parameter and Switch Value Status, 1 RS485 (Modbus-RTU)
|
AMC16Z-FAK48
|
Measure A+B Two-way AC Outlet, Total 48 Branch Full Electric Parameter and Switch Value Status, 1 RS485 (Modbus-RTU)
|
AMC16Z-FDK24
|
Measure A+B Two-way DC Outlet, Total 24 Branch Full Electric Parameter and Switch Value Status, 1 RS485 (Modbus-RTU)
|
AMC16Z-FDK48
|
Measure A+B Two-way DC Outlet, Total 48 Branch Full Electric Parameter and Switch Value Status, 1 RS485 (Modbus-RTU)
|
Technical Parameter
|
Value
|
|
Measured Parameters
|
Voltage, Current, Power, Electric Energy, Ambient Temperature and Humidity
|
|
Bus Voltage
|
Rated
|
48V DC, 240V DC, 336V DC
|
Measured Range
|
±20%
|
|
Overload
|
Instantaneous Voltage 2 Times/Second
|
|
Current Incoming Line Circuit
|
Rated
|
5V (Hall Sensor, Powered by AMC 16Z-ZD ±12V)
|
Overload
|
Duration 1.2 Times, Instantaneous 10 Times/Second
|
|
Temperature and Humidity
|
Temperature Range
|
-40ºC-+99ºC
|
Humidity Range
|
20%-90%
|
|
Measurement Precision
|
Incoming Line
|
Voltage/Current Class 0.5, Power/Electric Energy Class 1
|
Temperature
|
±1ºC
|
|
Humidity
|
±5%
|
|
Auxiliary Power
|
Single Take Electricity (≤15W)
|
|
Environment
|
Temperature
|
Work: -10ºC-45ºC Storage: -25ºC-70ºC
|
Humidity
|
Relative Humidity ≤95%
|
|
Altitude
|
≤2000m
|
|
Switching Output
|
2 Way 3A 250VAC / 3A 30VDC
|
|
Switching Input
|
6 Way Dry Contact
|
|
Communication
|
RS485 / Modbus-RTU
|
|
Installation
|
Din 35mm Guide Rail or Floor Mounted
|
|
Protection Grade
|
IP20
|
|
Pollution Levels
|
2
|
|
Security
|
Insulation
|
All Terminals and the Insulation Resistance Between the Conductive Pieces Not Below 100MΩ
|
Pressure
|
A Circuit Voltage and Current Signal // B Circuit Voltage and Current Signal // Switching Output // Other Ports Should Meet AC 2kV 1min Between Pairs, Switching Input and Other Ports Should Meet AC 0.5kV 1min, Leakage Current Should be Less Than 2mA, No Breakdown or Flash Over Phenomenon
|
|
Electromagnetic Compatibility
|
Anti Static Interference
|
Class 4
|
Resistance to Rapid Transient Pulse Groups
|
Class 3
|
|
Resistant to Surge Interference
|
Class 4
|
|
Radio Frequency Electromagnetic Radiation
|
Class 3
|