Theory: | Electromagnetic Relay |
---|---|
Usage: | Current Relay |
Phase: | 3 |
Samples: |
---|
Customization: |
---|
Shipping Cost:
Estimated freight per unit. |
about shipping cost and estimated delivery time. |
---|
Payment Method: | |
---|---|
Initial Payment Full Payment |
Currency: | US$ |
---|
Return&refunds: | You can apply for a refund up to 30 days after receipt of the products. |
---|
Suppliers with verified business licenses
Technical Parameter
|
Value
|
||
AC Type
|
A Type
|
||
Input
|
Rated Residual Operated Current I△n
|
0.03, 0.1, 0.3, 0.5(A)
|
0.03, 0.05, 0.1, 0.3, 0.5, 1, 3, 5, 10, 30(A) Note1
|
Limited Non-actuating Time
|
0.1, 0.5(S)
|
0, 0.06, 0.1, 0.2, 0.3, 0.5, 0.8, 1, 4, 10(S) Note2
|
|
Rated Residual Non-operating Current I△
|
50% I△n
|
Adjustable
|
|
Features
|
Sinusoidal AC Current
|
Sinusoidal AC Current and Pulsating DC Current
|
|
Frequency
|
50Hz±5Hz
|
||
Tripping Accuracy
|
-20%~-10% I△n
|
||
Output
|
Output Mode
|
1 NC Contact, 1 Normal Change Over Contact
|
1 NC Contact, 1 Normal Change Over Contact, All Adjustable
|
Contact Capacity
|
5A/250VAC, 5A/30VDC
|
AL1: 8A/250VAC, 5A/30VDC; AL2: 6A/250VAC, 5A/30VDC
|
|
Reset Mode
|
Local, Remote
|
Local, Remote, Automatic
|
|
Auxiliary Power Supply
|
Voltage Range
|
AC110V, AC220V (+-10%)
|
AC/DC 85-270V
|
Power Consumption
|
≤5W
|
||
Power Frequency Withstand Voltage
|
The effective value of alternating current between the power supply, input and output: 2kV/min
|
||
Environment
|
Temperature
|
Operation: -20~+55 degrees Celsius, Storage: -30~-70 degrees Celsius
|
|
Humidity
|
≤95% RH (No Condensation)
|
||
Altitude
|
≤2000m
|
Type
|
Function
|
Option
|
ASJ20-LD1C
|
Measurement of type AC residual current
Alarm when the residual current exceeds the set value
Adjustable rated residual current from 0.03 to 0.5A
Adjustable limiting no-actuating time from 0.1s to 0.5s
2 relay output (1 NC contact, 1 normal change over contact)
Local/remote "test" and "reset function"
|
/
|
ASJ20-LD1A
|
Measurement of type AC residual current
Residual current percentage light bar indication (30%, 50%, 70%, TRIP)
Adjustable rated residual current from 0.03 to 0.5A
Adjustable limiting no-actuating time from 0.1s to 10s
2 programmable relay output (1 NC contact, 1 normal change over contact)
Local/remote/automatic "test" and "reset" function
|
/
|
ASJ10-LD1C
|
Measurement of type AC residual current
Alarm when the residual current exceeds the set value
Adjustable rated residual current from 0.03 to 0.5A
Adjustable limiting no-actuating time from 0.1s to 0.5s
2 relay output (1 NC contact, 1 normal change over contact)
Local/remote "test" and "reset function"
|
/
|
ASJ10-LD1A
|
Measurement of type AC residual current
Residual current percentage light bar indication (30%, 50%, 70%, TRIP) Adjustable rated residual current from 0.03 to 0.5A
Adjustable limiting no-actuating time from 0.1s to 10s
2 programmable relay output (1 NC contact, 1 normal change over contact)
Local/remote/automatic "test" and "reset" function
|
/
|
ASJ10L-LD1A
|
Measurement of type AC residual current
Continuously adjustable of rated residual current from 0.03 to 30A
Continuously adjustable of limiting no-actuating time from 0.1s to 10s 2 programmable relay output (1 NC contact, 1 normal change over contact) Local/remote/automatic "test" and "reset" function
Multi-function LCD display
RS485 communication with Modbus-RTU protocol
|
/C: RS485
|
Suppliers with verified business licenses