Display: | No Display |
---|---|
Installation: | Direct Connected |
Usage: | Multi-Functional Energy Meter, Watt-Hour Meter, Standard Electric Energy Meter, Reactive Energy Meter |
Electric Equipment: | Three-phase Four-wire |
Theory: | Electronic Meter |
Power Meter Connection: | Terminal |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
AMC16Z-FA can measure electrical parameters of 3 phase in 8 circuits(single phase 24 circuits), such as line voltage, phase voltage, zero sequence
voltage, line current, phase current, zero sequence current, active power, reactive power, power factor, frequency, active energy, reactive energy etc.
Also, the meter has RS485 agreeing with the Modbus RTU Integration.
It can replace DZS900 Heyuan meter.
Model
|
AMC16Z-FD
|
||
Measuring parameters
|
voltage,current,power energy or DI DO
|
||
Busbar voltage
|
Rated voltage
|
48VDC,240VDC or 336VDC
|
|
Measuring range
|
±20%
|
||
overload
|
instant voltage 2 times/second
|
||
current outlet circuit
|
Rated range
|
5V(hall effect current sensor AHKC-EKA,Needs power supply ±12V)
|
|
overload
|
sustained 1.2times,instantaneous current 10times/second
|
||
accuracy
|
outlet
|
current,voltage class: 0.5 power,energy: 1
|
|
Auxiliary power supply
|
DC12V-24V
|
||
Communication
|
RS485/Modbus-RTU
|
||
Installation
|
DIN35mm or panel type
|
||
Waterproof level
|
IP20
|