Customization: | Available |
---|---|
After-sales Service: | 2 Years |
Warranty: | 2 Years |
Still deciding? Get samples of US$ 2100/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | AIM-M10 | ||
auxiliary power supply | |||
Voltage | DC24V( fluctuation range ±25%) | ||
Max power consumption | <3VA | ||
insulation monitoring | |||
Insulation resistance measuring range | 10~999kΩ | ||
Relative percentage accuracy | 0~±10% | ||
Alarm value range | 50~999kΩ | ||
Response time | <2S | ||
Measuring voltage | <12V | ||
Measuring current | <50μA | ||
Current monitoring | |||
Measuring range | 2.1~50A | ||
Alarm value range | 5~50A | ||
Measuring accuracy | class 5 | ||
Display | Digital and percentage display | ||
Temperature monitoring | |||
thermal resistor | PT100 | ||
Measuring range | -50ºC~+200ºC' | ||
Alarm value range | 0ºC~+200ºC' | ||
Alarm output | |||
Output type | 2 channel relay output(unable to program) | ||
Contact rating | AC 250V/3A DC30V/3A | ||
Environment | |||
Working temperature | -10ºC~+55ºC' | ||
Storage temperature | -20ºC+70ºC' | ||
Relative humidity | 5%~95%,non-condensing | ||
Altitude | ≤2500m | ||
Communication | |||
one channel RS485,MODBUS-RTU 1 channel CAN interface,user-defined | |||
Rated impulse voltage/pollution class | |||
4KV/III | |||
EMC and electromagnetic radiation | |||
In accordance with IEC1326-2-4 |
name
|
model
|
Insulation monitor
|
AIM-M200
|
Power module
|
DR-60-24
|
Isolation transformer
|
AITR8000
|
Current Transformer
|
AKH-0.66P26
|
test signal generator
|
ASG150
|
insulation fault locator
|
AIL150-4
|
centralized remote alarm indicator
|
AID150
|