Customization: | Available |
---|---|
Display: | Digital |
Installation: | Indirect Connected |
Still deciding? Get samples of US$ 301/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Parameters of AEW210-D16-4S(LCD display,3 phase 4 circuit power metr with 12 CTs)
|
|||
Input Voltage
|
AC 3X220/380V
|
||
Input Current
|
max up to 100A
|
||
Frequency
|
45~65HZ
|
||
Accuracy
|
0.05Hz(frequency);0.5(voltage,current);1(active energy);2(reactive energy);±%(2-31st harmonics)
|
||
Switching value
|
pulse output:Dry contact input,in-built power supply
|
||
relay NO contact output;contact capacity:AC250V/3A DC30V/3A
|
|||
Communication
|
RS485,Modbus-RTU;baud rate 1200-38400
|
||
Basic functions
|
|||
3 phase voltage,current,zero sequence current and frequency measuring
|
|||
3 phase power,total power(active,reactive and apparent power),power factor and total power factor measuring
|
|||
voltage current phase angle,current voltage unbalance
|
|||
2-31st sub harmonic and total harmonic analysis(voltage and current)
|
|||
extreme value record of voltage,current and power in this month and last month
|
|||
max current,real current and power kwh max demand
|
|||
200 SOE,record DI and DO
|
|||
Support alarm output: over voltage,over current,phase loss,DI linkage and so on
|
|||
4 time zones and 14 time periods multi tariff setting
|
|||
4 quadrants energy,12 months multi tariff energy couting
|
|||
31 days 4 quadrant and multi tariff energy frozen
|
|||
accuracy:active energy class 1,reactive energy class 2
|
|||
2DI2DO,1 active pulse output
|
Extended function(optional)
|
|||
Switching value module(MK)
|
12 DI
|
12 DI, relay NO contact input and in-built power supply
|
|
4 DO
|
4 DO, relay NO contact output;contact capacity:AC250V/3A DC30V/3A
|
||
Communication
|
RJ45,modbus-rtu(communicate with ADW210 module
|
||
power supply
|
RJ45,DC12V
|
||
Temperature and leakage current module(MTL)
|
Temperature measuring
|
NTC input,range:-20ºC-100ºC
|
|
Leakage current measuring
|
residual current transformer :10-3000mA
|
||
Accuracy
|
Temperature:±1ºC,leakage current:1
|
||
Communication
|
RJ45,modbus-rtu(communicate with ADW210 module
|
||
power supply
|
RJ45,DC12V
|
Instrument type
|
Dimensions(mm)
|
|||
length
|
width
|
height
|
length(with terminal block)
|
|
ADW210
|
87.8
|
72
|
71.5
|
97.7
|
ADW210 module size
|
87.8
|
36
|
71.5
|
105.5
|
CTs
|
Dimensions(mm)
|
Hole size(mm)
|
|||||
W
|
H
|
D
|
M
|
N
|
Φ1
|
Φ2
|
|
AKH-0.66/K-Φ16N
|
31
|
50
|
36
|
27
|
42
|
16
|
17
|