Type: | Open-Loop |
---|---|
Accuracy Grade: | 1.0G |
IP Rating: | IP44 |
Samples: |
---|
Customization: |
---|
Shipping Cost:
Estimated freight per unit. |
about shipping cost and estimated delivery time. |
---|
Payment Method: | |
---|---|
Initial Payment Full Payment |
Currency: | US$ |
---|
Return&refunds: | You can apply for a refund up to 30 days after receipt of the products. |
---|
Suppliers with verified business licenses
Type
|
Rated Input
|
Auxiliary Power
|
Rated Output
|
Measuring Aperture
(mm)
|
|
AHKC-EKA
|
0-(50-500)A
|
±15V
|
5V/4V
|
Φ20
|
Split
|
AHKC-EKAA
|
DC 0-(50-500)A
|
12V/24V
|
4-20mA
|
||
AHKC-EKDA
|
AC 0-(50-500)A
|
12V/24V
|
4-20mA
|
||
AHKC-EKB
|
0-(200-1000)A
|
±15V
|
5V/4V
|
Φ40
|
Split
|
AHKC-EKBA
|
DC 0-(200-1000)A
|
12V/24V
|
4-20mA
|
||
AHKC-EKBDA
|
AC 0-(200-1000)A
|
12V/24V
|
4-20mA
|
||
AHKC-EKC
|
0-(500-1500)A
|
±15V
|
5V/4V
|
Φ55
|
Split
|
AHKC-EKCA
|
DC 0-(500-1500)A
|
12V/24V
|
4-20mA
|
||
AHKC-EKCDA
|
AC 0-(500-1500)A
|
12V/24V
|
4-20mA
|
||
AHKC-K
|
0-(400-2000)A
|
±15V
|
5V/4V
|
64*16
|
Split
|
AHKC-KAA
|
DC 0-(400-2000)A
|
12V/24V
|
4-20mA
|
||
AHKC-KDA
|
AC 0-(400-2000)A
|
12V/24V
|
4-20mA
|
||
AHKC-H
|
0-(500-3000)A
|
±15V
|
5V/4V
|
82*32
|
Split
|
AHKC-KA
|
104*36
|
||||
AHKC-HB
|
0-(2000-8000)A
|
±15V
|
5V/4V
|
132*52
|
Split
|
0-(10000-20000)A
|
|||||
0-(25000-40000)A
|
|||||
AKHC-HBAA
|
DC 0-(2000-8000)A
|
12V/24V
|
4-20mA
|
132*52
|
Split
|
DC 0-(10000-20000)A
|
|||||
DC 0-(25000-40000)A
|
|||||
AKHC-HBDA
|
AC 0-(2000-8000)A
|
12V/24V
|
4-20mA
|
132*52
|
Split
|
AC 0-(10000-20000)A
|
Technical Parameters
|
Open-loop
|
||
Real-time Values
|
Hall (ture RMS)
|
||
Output
|
Normal Value
|
Voltage: ±5V/4V
|
Current: 4-20mA
|
Zero Offset Voltage (Current)
|
Voltage: ±20mV
|
Current: ±0.05mA
|
|
Offset Voltage (Current) Drift
|
Voltage: ≤±1.0mV/ºC
|
Current: ±0.04mA/ºC
|
|
Linearity
|
≤0.2%FS
|
||
Power Voltage
|
DC ±15V DC 12V/24V
|
DC 12V/24V
|
|
Bandwidth
|
0-20kHz
|
||
Response Time
|
≤5μs
|
≤300ms
|
|
Dielectric Strength
|
Permissible 3500VAC between input/output
|
||
Accuracy Class
|
1.0
|
||
Environment
|
Temperature
|
-40ºC-+85ºC
|
|
Humidity
|
Up to 95%, no condensing
|
||
Altitude
|
≤3500m
|
Specification/Size
|
Outline Size(mm)
|
Through Size(mm)
|
Mounting Size(mm)
|
Figure
|
|||||
W
|
H
|
D
|
a
|
e
|
Φ
|
M
|
N
|
||
AHKC-EKA
|
60
|
64
|
16
|
/
|
/
|
20
|
47
|
/
|
Fig.1
|
AHKC-EKAA
|
|||||||||
AHKC-EKDA
|
|||||||||
AHKC-EKB
|
100
|
102
|
24
|
/
|
/
|
40
|
80
|
/
|
Fig.1
|
AHKC-EKBA
|
|||||||||
AHKC-EKBDA
|
|||||||||
AHKC-EKC
|
115
|
110
|
27
|
/
|
/
|
55.5
|
95.5
|
/
|
Fig.1
|
AHKC-EKCA
|
|||||||||
AHKC-EKCDA
|
|||||||||
AHKC-K
|
127
|
63
|
25
|
64
|
16
|
/
|
/
|
30
|
Fig.2
|
AHKC-KAA
|
|||||||||
AHKC-KDA
|
|||||||||
AHKC-H
|
149
|
79
|
25
|
82
|
32
|
/
|
/
|
46
|
Fig.2
|
AHKC-KA
|
176
|
95.5
|
29
|
104
|
36
|
/
|
/
|
60
|
Fig.2
|
AHKC-HB
|
204
|
111.5
|
29
|
132
|
52
|
/
|
/
|
48*2
|
Fig.2
|
AHKC-HBAA
|
|||||||||
AHKC-HBDA
|
Suppliers with verified business licenses