After-sales Service: | 2 Years |
---|---|
Warranty: | 2 Years |
Display: | Digital |
Installation: | Direct Connected |
Usage: | Multi-Functional Energy Meter, Watt-Hour Meter, Meter for Industry and Home Use, Standard Electric Energy Meter, Reactive Energy Meter, Multi-rate Watt-hour Meters, Maximum Demand Meter |
Electric Equipment: | 3p3w 3p4w |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
General
APM series meters have full power measurement, energy statistics, analysis of power quality and network communications and other functions, are mainly used for comprehensive monitoring of the quality of power supply network
Option Function
/F: muti tariff(shares) energies
/MD82: 8DI+2DO
/MLOG: SD Card
/MA84: 8AI+4AO
/MCM: the second RS485
/MCE: Ethernet
/MCP: Profibus(Profibus-DP)
Model
|
APM800/MCE
|
||
Dimension
|
|||
Panel size
|
96*96mm
|
||
Cut out
|
92*92mm
|
||
Depth
|
71mm
|
||
Technical data
|
|||
Input
|
Net
|
three-phase three-wire,three-phase four-wire
|
|
Frequency
|
45~65HZ
|
||
Voltage
|
rated value
|
AC100V 110V 400V 690V
|
|
overload
|
1.2times rated value(contineously);2times rated value/1second
|
||
power consumption
|
<0.5VA(every channel)
|
||
Current
|
rated value
|
AC 1A,5A,4mm2 wire can be connected
|
|
overload
|
1.2times rated value(contineously);10times rated value/1second
|
||
power consumption
|
<0.5VA(every channel)
|
||
Accuracy
|
voltage current power consumption
|
0.5s
|
|
active electrical energy
|
0.5s
|
||
reactive electrical energy
|
2s
|
||
harmonic
|
class 1
|
||
Digital input
|
dry contact input,inner power supply
|
||
Relay output
|
contact type:main body normal open,module changeover contact; contact capacity:AC250V/3A DC30V/3A
|
||
Impulse output
|
output type optcoupler impulse
|
||
Analog output
|
DC 0~20mA,4~20mA,0~5V,1~5V
|
||
Analog input
|
DC 0~20mA,4~20mA,0~5V,1~5V
|
||
Communication
|
RS485/Modbus-RTU communication and DLT645 protocol;
|
||
RS232/Profibus-DP protocol;
|
|||
RJ45(Ethernet)/Modbus-TCP,http and DHCP protocol...
|
|||
Power supply
|
work range
|
AC85V~265VDC 100V~350V or AC100~415VDC 125V~500V
|
|
power consumption;main body power consumption≤15VA
|
|||
Safety
|
Power frequency withstand voltage
|
The power frequency with stand voltage between the shell and the auxiliary power supply, each input and output terminal group is AC4kV/1min;
The power frequency withstand voltage between the auxiliary power supply and each input and each output terminal group is AC2kV/1min;
The power frequency withstand voltage between the voltage input and other input/output terminal groups is AC2kV/1min; The power frequency withstand voltage between the current input and other input/output terminal groups is AC2kV/1min; The power frequency withstand voltage between the relay output and other input/output terminal groups is AC2kV/1min; The power frequency withstand voltage between each terminal group of switch input,communication,analog output and pulse output isAC1kV/1min; |
|
Insulation resistance
|
Inputs,outputs to the shell>100MΩ;
|
||
Electromagnetic compatibility
|
Meet IEC61000 standard(Level4);
|
||
Environment
|
Operating temperature:-20°C~+65°C;Storage temperature:-20°C~+70°C;
Relative humidity:≤95%without condensation; Altitude:≤2500m; |